Agency Approvals | : | UL 916, European conformance CE:EN 60730-1, EN 60730-2-9, EN 60730-2-13,EN 61000-6-2, EN 61000-6-3, EN61000 Series - IndustrialImmunity, EN 61326-1FCC Part 15 Class B, REACH, RoHS, ICES-003 (Canada), UKCA(UK) |
CO2 Measurement Accuracy | : | ±30 ppm ±3% of measured value |
CO2 Measurement Range | : | 0 to 10,000 ppm |
CO2 Measurement Repeatability | : | ±20 ppm ±1% of measured value |
CO2 Response Time | : | <60 seconds for 90% step change |
CO2 Sensor Type | : | Non-dispersive infrared (NDIR), diffusion sampling |
Display Size | : | 61 mm (2.4 in) |
Display Type | : | LCD, Color, Backlit, Capacititve Touchscreen |
Fan Speed Setpoint Range | : | Off, Low, Medium, High, Auto |
Housing Material | : | High-impact ABS plastic |
Humidity Output Range | : | 0 to 100% RH |
Humidity Sensor Accuracy | : | ±3.8% RH from 10 to 60% RH @ 25°C (77 °F)±4.8% RH from 60 to 80% RH @ 25°C (77 °F)±5.8% RH from 80 to 100% RH @ 25°C (77 °F) |
Humidity Sensor Type | : | Solid state capacitive |
Humidity Setpoint Range | : | Scale: 0 to 100% RH |
Humidity Stability | : | ±1% @ 20°C (68 °F) annually for 2 years |
IP Rating | : | IP30 |
Input Power | : | Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz |
Operating Humidity | : | 0 to 95% RH non-condensing |
Operating Temperature | : | 0 to 50 °C (32 to 122 °F) |
Output Specifications | : | BACnet or Modbus via RS-485, selectable |
Outputs | : | Protocol Output |
Override | : | Display models feature momentary override button |
PM Accuracy | : | PM 1 and PM 2.5:0 to 100 μg/m³ +/-[5μg/m³+5% m.v.],100 to 1000 ug/m³ +/-[10% m.v.]PM 4 and PM 10*:0 to 100 μg/m³ +/-[25μg/m³],100 to 1,000 μg/m³ +/-[25% m.v.](sensor-to-sensor deviation) |
PM Mass Concentration Range | : | 0 to 1,000 μg/m³ |
Temperature Accuracy | : | ±0.2 °C (±0.4 °F) typical |
Temperature Coefficient | : | ±0.1% RH/°C above or below 25 °C(77 °F) typical |
Temperature Measurement Range | : | 0 to 50 °C (32 to 122 °F) |
Temperature Measurement Resolution | : | 0.1 °C (0.1 °F) |
Temperature Sensor Type | : | Solid state, integrated circuit |
Temperature Setpoint Range | : | Scale: 0 to 50 °C (32 to 122 °F) max.,adjustable span |
Terminal Block Torque | : | 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf ) |
Terminal Blocks | : | Screw terminals, 18-24 AWG |
VOC Measurement Accuracy | : | ±15% of measured value |
VOC Measurement Range | : | 0 to 100% AQI for VOC |
VOC Output Scale | : | 0 to 1,000 ppb of total VOC (TVOC) |
VOC Sensor Type | : | Solid state |
PMW Protocol Wall Particulate Matter (PM) Sensor is a multi sensor platform great for living spaces. It is designed for use with BAS controllers accepting BACnet or Modbus outputs. The PMWTPC2AV air quality sensor measures CO2, Temperature, Humidity, VOC and Particulate Matter. The new PMW Protocol series offers reliability offering PM measurement options of PM1, PM2.5, PM4.0, and PM10 to cover different Particulate Matter sizes. It also has a high accuracy CO2 measurement Dual Beam Non-Dispersive infrared technology up to ±20 ppm ±1% of measured value.
This sensor is easy to use, easy to install and easy to maintain. It’s snap on cover with security screw makes installation easy and it also self calibrates making it easier to maintain. The PMWTPC2AV has a touch screen interface and a visual CO2 and PM indication making it easier to use and to detect issues early.