Agency Approvals | : | UL 916, European conformance CE:EN 60730-1, EN 60730-2-9, EN 60730-2-13,EN 61000-6-2, EN 61000-6-3, EN 61000 Series - industrialimmunity, EN 61326-1FCC Part 15 Class B, REACH, RoHS, ICES-003 (Canada), UKCA(UK) |
CO2 Measurement Accuracy | : | ±30 ppm ±3% of measured value |
CO2 Measurement Range | : | 0 to 2000/5000 ppm (selectable) |
CO2 Measurement Repeatability | : | ±20 ppm ±1% of measured value |
CO2 Response Time | : | <60 seconds for 90% step change |
CO2 Sensor Type | : | Non-dispersive infrared (NDIR), diffusion sampling |
Display Size | : | 61 mm (2.4 in) |
Display Type | : | LCD, Color, Backlit, Capacititve Touchscreen |
Fan Speed Setpoint Range | : | 0 to 10V outputOff 0V, Auto 1.5V, Low 3.3V, Med. 6.7V, High 10.0V |
Housing Material | : | High-impact ABS plastic |
Humidity Measurement Linearity | : | Included in accuracy specification |
Humidity Output Range | : | 0 to 100% RH |
Humidity Sensor Accuracy | : | ±3.8% RH from 10 to 60% RH @ 25°C (77 °F)±4.8% RH from 60 to 80% RH @ 25°C (77 °F)±5.8% RH from 80 to 100% RH @ 25°C (77 °F) |
Humidity Sensor Type | : | Solid state capacitive, replaceable |
Humidity Setpoint Range | : | 0 to 10V outputScale: 0 to 100% RH |
Humidity Stability | : | ±1% @ 20°C (68 °F) annually for 2 years |
IP Rating | : | IP30 |
Input Power | : | Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz |
Operating Humidity | : | 0 to 95% RH non-condensing |
Operating Temperature | : | 0 to 50 °C (32 to 122 °F) |
Output Specifications | : | Selectable 4 To 20 MA, 0 To 5 V, 0 To 10 V |
Outputs | : | Analog Output |
Override | : | Display models feature momentary-to-ground overridebutton |
PM Accuracy | : | PM 2.5: 0 to 100 μg/m³ +/-[5μg/m³+5% m.v.],100 to 1000 ug/m³ +/-[10% m.v.] |
PM Mass Concentration Range | : | 0 to 1,000 μg/m³ |
Temperature Accuracy | : | ±0.2 °C (±0.4 °F) typical |
Temperature Coefficient | : | ±0.1% RH/°C above or below 25 °C(77 °F) typical |
Temperature Measurement Range | : | 0 to 50 °C (32 to 122 °F) |
Temperature Measurement Resolution | : | 0.1 °C (0.1 °F) |
Temperature Sensor Type | : | Solid state, integrated circuit |
Temperature Setpoint Range | : | 0 to 10V outputScale: 10 to 35 °C (50 to 95 °F) /0 to 50 °C (32 to 122 °F) |
Terminal Block Screw Torque | : | 0.2 N-m (2.0 in-lbF) max. |
Terminal Blocks | : | Screw terminals, 18-24 AWG |
PMW Analog Wall Particulate Matter (PM) Sensor is a multi sensor platform great for living spaces. It is designed for use with BAS controllers accepting 4 to 20 mA, o to 5Vdc or 0 to 10 Vdc outputs. The PMWTACA air quality sensor measures CO2, Temperature, Humidity and Particulate Matter. It has a high accuracy CO2 measurement Dual Beam Non-Dispersive infrared technology up to ±20 ppm ±1% of measured value.
This sensor is easy to use, easy to install and easy to maintain. It’s snap on cover with security screw makes installation easy and it also self calibrates making it easier to maintain. The PMWTACA has a touch screen interface and a visual CO2 and PM indication making it easier to use and to detect issues early.