Agency Approvals | : | UL 916; CE: EN61000-6-2, EN61000-6-3, EN61000 Series, immunity, EN 61326-1; FCC Part 15 Class A; REACH, RoHS, RoHS 2 (China), RCM (Australia), ICES-003 (Canada), UKCA (UK) |
Collection | : | Plant Room Air Quality Sensors |
Enclosure Material | : | Polycarbonate; flammability rating UL 94 V0 |
Humidity Calibration Certificate | : | Replaceable RH element available in 1% & 2% with NISTcalibration certificate |
Humidity Measurement Accuracy | : | ±2% from 10 to 80% RH @ 25°C (77 °F) |
Humidity Measurement Linearity | : | Included in accuracy specification |
Humidity Measurement Resolution | : | 0.1% RH |
Humidity Output Range | : | 0 to 100% RH |
Humidity Sensor Type | : | Solid state capacitive, replaceable |
IP Protection | : | IP65 |
Input Specifications | : | 3-wire volt mode: 20 to 30 Vdc, 24 Vac, 50 to 60 Hz; loop powered: 20 to 30 Vdc |
Measurement Type | : | Relative Humidity / Temperature |
Operating Humidity | : | 0 to 95% RH non-condensing |
Operating Temperature | : | -35 to 60 °C (-31 to 140 °F) |
Output Specifications | : | Selectable 4 To 20 MA, 0 To 5 V, 0 To 10 V |
Outputs | : | Analog Output |
Temperature Measurement Accuracy | : | ±0.2 °C (±0.4 °F) typical |
Temperature Measurement Range | : | -35 to 60 °C (-31 to 140 °F) |
Temperature Measurement Resolution | : | 0.1 °C (0.1 °F) |
Temperature Sensor Type | : | 10K Type 2 Thermistor |
Terminal Blocks | : | Screwless terminal block with spring actuator, 16-24 AWG |
HD2 Series Analog Humidity Sensors provide an ideal solution for measuring relative humidity in a wide range of conditions. All models are equipped with a solid state capacitive humidity sensor that is easy to replace in the field. They are also equipped with a solid state temperature sensor that provides high accuracy measurements.
HD2XA2D is an all-in-one device combining humidity and temperature sensing. Intended for duct mount applications, the device ensures a building’s optimum temperature and humidity levels, resulting in greater energy efficiency. Each device is an active sensor that converts a humidity or temperature measurement into 4-20mA, 0 to 5 Vdc or 0 to 10 Vdc analog output.