• We can help. Call 800-354-8556

Veris CD2LAXAVP Duct Air Quality Sensor

Sensor, CO2, Duct, LCD, Temp Trans, VOC, Particulate Matter

  • Brand Name: Veris
  • Veris Part#: CD2LAXAVP
  • Est. Shipping Date: loading
Agency Approvals      :      UL 916; CE: EN61000-6-2, EN61000-6-3, EN61000 Series, immunity, EN 61326-1; FCC Part 15 Class A; REACH, RoHS, RoHS 2 (China), RCM (Australia), ICES-003 (Canada), UKCA (UK)
CO2 Measurement Accuracy      :      ±30 ppm ±3% of measured value
CO2 Measurement Range      :      0 to 5000 ppm
CO2 Measurement Repeatability      :      ±20 ppm ±1% of measured value
CO2 Measurement Resolution      :      1 ppm
CO2 Response Time      :      <60 seconds for 90% step change
CO2 Sensor Type      :      Non-dispersive infrared (NDIR), diffusion sampling
Collection      :      Plant Room Air Quality Sensors
Display Resolution      :      CO2: 1 ppm, Temp: 0.1 °C or °F, VOC: 1% AQI, PM: 1 μg/m³
Display Type      :      LCD, Positive Display with Backlight
Enclosure Material      :      Polycarbonate; flammability rating UL 94 V0
IP Protection      :      IP65
Input Specifications      :      Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Measurement Type      :      CO2 | VOC | Particulate Matter | Temperature
Measurement Values Displayed      :      CO2: ppm, Temp: °C or °F, VOC: AQI, PM: μg/m³
Operating Humidity      :      0 to 95% RH non-condensing
Operating Temperature      :      -25 to 70 °C (-13 to 158 °F)
Output Specifications      :      Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
Outputs      :      Analog Output
PM Accuracy      :      PM 1 and PM 2.5: ±10 μg/m³ (0 to 100 μg/m³), ±10% (100 to 1000 μg/m³)PM 4 and PM 10: ±25 μg/m³ (0 to 100 μg/m³), ±25% (100 to 1000 μg/m³)
PM Mass Concentration Range      :      ±1 μg/m³
PM Particulate Size      :      PM1.0, PM2.5, PM4.0, PM10
PM Resolution      :      ±1 μg/m³
PM Sensor Type      :      Laser-scatter
Temperature Measurement Accuracy      :      ±0.2 °C (±0.4 °F) typical
Temperature Measurement Range      :      0 to 50 °C (32 to 122 °F)
Temperature Measurement Resolution      :      0.1 °C (0.1 °F)
Temperature Sensor Type      :      Solid state, integrated circuit
Terminal Blocks      :      Screwless terminal block with spring actuator, 16-24 AWG
VOC Measurement Accuracy      :      ±15% of measured value
VOC Measurement Range      :      0 to 100% AQI for VOC
VOC Output Scale      :      0 to 1,000 ppb of total VOC (TVOC)
VOC Sensor Type      :      Solid state
Warranty      :      5 years

CD2 Series Air Quality Sensors are duct mount all-in-one sensors for monitoring air quality. The CD2 series device combines CO2, temperature, humidity, VOC and particulate matter (PM) sensing into a single unit to ensure a building’s optimum air quality and energy efficiency. Each CD2LAXAVP device is an active sensor that converts a measurement into the following Analog output options: 4-20 mA, 0 to 5 Vdc or 0 to 10 Vdc

  • Analog output: 4-20 mA, 0 to 5 Vdc or 0 to 10 Vdc
  • LCD Positive Display with Backlight
  • Measurement Type: CO2/VOC/Particulate Matter/Temperature
  • Easy to Maintain: Self Calibrating
  • Easy to install: Latch on sensor cover and screwless terminal block wiring with spring actuator
  • Different models are available based on application requirements for lower-cost installations.
  • pdf Datasheet https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/CD2 Series_d0723.pdf
  • pdf Installation guide https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/CD2 Analog_GEX55248-00.pdf