• We can help. Call 800-354-8556

Veris CD2XP2AVP Duct Air Quality Sensor

Sensor, CO2, Duct, Humidity w/2%, Temp Trans, VOC, Particulate Matter, BAC/MB

  • Brand Name: Veris
  • Veris Part#: CD2XP2AVP
  • Est. Shipping Date: loading
Agency Approvals      :      UL 916; CE: EN61000-6-2, EN61000-6-3, EN61000 Series, immunity, EN 61326-1; FCC Part 15 Class A; REACH, RoHS, RoHS 2 (China), RCM (Australia), ICES-003 (Canada), UKCA (UK)
CO2 Measurement Accuracy      :      ±30 ppm ±3% of measured value
CO2 Measurement Range      :      0 to 5000 ppm
CO2 Measurement Repeatability      :      ±20 ppm ±1% of measured value
CO2 Measurement Resolution      :      1 ppm
CO2 Response Time      :      <60 seconds for 90% step change
CO2 Sensor Type      :      Non-dispersive infrared (NDIR), diffusion sampling
Collection      :      Plant Room Air Quality Sensors
Communication Specifications      :      BACnet MSTP or Modbus via RS-485, selectable
Communication      :      Protocol
Enclosure Material      :      Polycarbonate; flammability rating UL 94 V0
Humidity Calibration Certificate      :      Replaceable RH element available in 1% & 2% with NISTcalibration certificate
Humidity Measurement Accuracy      :      ±2% from 10 to 80% RH @ 25°C (77 °F)
Humidity Measurement Linearity      :      Included in accuracy specification
Humidity Measurement Resolution      :      0.1% RH
Humidity Output Range      :      0 to 100% RH
Humidity Sensor Type      :      Thin-film capacitive, replaceable
IP Protection      :      IP65
Input Specifications      :      Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Measurement Type      :      CO2 / VOC / Particulate Matter / Relative Humidity / Temperature
Operating Humidity      :      0 to 95% RH non-condensing
Operating Temperature      :      -25 to 70 °C (-13 to 158 °F)
PM Accuracy      :      PM 1 and PM 2.5: ±10 μg/m³ (0 to 100 μg/m³), ±10% (100 to 1000 μg/m³)PM 4 and PM 10: ±25 μg/m³ (0 to 100 μg/m³), ±25% (100 to 1000 μg/m³)
PM Mass Concentration Range      :      ±1 μg/m³
PM Particulate Size      :      PM1.0, PM2.5, PM4.0, PM10
PM Resolution      :      ±1 μg/m³
PM Sensor Type      :      Laser-scatter
Temperature Measurement Accuracy      :      ±0.2 °C (±0.4 °F) typical
Temperature Measurement Range      :      0 to 50 °C (32 to 122 °F)
Temperature Measurement Resolution      :      0.1 °C (0.1 °F)
Temperature Sensor Type      :      Solid state, integrated circuit
Terminal Blocks      :      Screwless terminal block with spring actuator, 16-24 AWG
VOC Measurement Accuracy      :      ±15% of measured value
VOC Measurement Range      :      0 to 100% AQI for VOC
VOC Output Scale      :      0 to 1,000 ppb of total VOC (TVOC)
VOC Sensor Type      :      Solid state
Warranty      :      5 Years

CD2 Series Air Quality Sensors are duct mount all-in-one sensors for monitoring air quality. The CD2 Series device combines CO2, temperature, humidity, VOC and particulate matter (PM) sensing into a single unit to ensure a building’s optimum air quality and energy efficiency. Each CD2XP2AVP device is an active sensor that converts a measurement into the following protocol output options: BACnet MS/TP, Modbus RTU

  • Measurement Type: CO2/VOC/Particulate Matter/Relative Humidity/Temperature
  • Protocol output: BACnet MS/TP, Modbus RTU
  • Easy to Maintain: Self Calibrating
  • Easy to install: Latch on sensor cover and screwless terminal block wiring with spring actuator
  • Different models in series are available based on application requirements for lower-cost installations.
  • pdf Datasheet https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/CD2 Series_d0723.pdf
  • pdf Installation guide https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/CD2 Protocol_GEX55250-00.pdf