Veris CWE2C Economy Wall Air Quality Sensor

Sensor, CO2, Economy, Wall,Temp,1K PT

  • Brand Name: Veris
  • Veris Part#: CWE2C
  • Est. Shipping Date: loading
CO2 Measurement Accuracy      :      ±30 ppm ±3% of measured value
CO2 Measurement Range      :      0 to 2000ppm
CO2 Measurement Repeatability      :      ±20 ppm ±1% of measured value
CO2 Measurement Resolution      :      1 ppm
CO2 Response Time      :      =75 seconds for 90 degree step change
CO2 Sensor Type      :      Dual beam non-dispersive infrared (NDIR), diffusion sampling
Color      :      Matte White
Electrical Wiring Size      :      Screw terminals, 18-24 AWG
Enclosure Material      :      High impact ABS plastic
Humidity Measurement Accuracy      :      ±2% from 10 to 80% RH @ 25°C (77 °F)
IP Protection      :      IP20
Input Specifications      :      Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Measurement Type      :      CO2 / Temperature
Operating Current      :      20mA
Operating Humidity      :      0 to 95% RH non-condensing
Operating Temperature      :      0 to 50 °C (32 to 122 °F)
Output Specifications      :      Selectable 4 to 20 mA (2-wire), 0 to 5 V (3-wire), 0 to 10 V (3-wire)
Outputs      :      Analog
Standards EMC      :      EN61000 Series - industrial immunity
Standards      :      CE, UL 916, RCM, ICES-003. REACH, RoHS
Temperature Measurement Accuracy      :      ±0.3 °C (±0.54 °F) typical
Temperature Measurement Range      :      0 to 50 °C (32 to 122 °F)
Temperature Measurement Resolution      :      0.1 °C (0.1 °F)
Temperature Sensor Type      :      1000 Ohm Platinum RTD
Warranty      :      3 Years

The CWE2 Series of air quality sensors for living space are for use with BAS controllers designed to accept 4 to 20mA, 0 to 5 Vdc or 0 to 10 Vdc outputs. These sensors measure CO2 levels using a dual-beam, non-dispersive infrared (NDIR) technology. The CWE2C measures temperature as well. The CWE2 Series Economy sensor has an accuracy of ±30 ppm ±3% of measured value, features 2-wire 4 to 20mA and 3-wire voltage outputs.

  • NDIR CO2 sensor
  • 1000 Ohm Platinum RTD temperature sensor
  • Temperature accuracy: ±0.3 °C (±0.54 °F) typical
  • Lower Installation costs: 2 wire current outputs
  • Competitively priced sensors
  • Easy installation: large wiring terminals on baseplate screw simplify installation and service
  • Flexibility: field selectable outputs
  • Easy to maintain: self calibrating
  • pdf Datasheet https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/CWE2_CWV2_d0624.pdf
  • pdf Installation guide https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/CWE2 Analog_i0f2.pdf