CO2 Measurement Accuracy | : | ±30 ppm ±3% of measured value |
CO2 Measurement Range | : | 0 to 2000ppm |
CO2 Measurement Repeatability | : | ±20 ppm ±1% of measured value |
CO2 Measurement Resolution | : | 1 ppm |
CO2 Response Time | : | =75 seconds for 90 degree step change |
CO2 Sensor Type | : | Dual beam non-dispersive infrared (NDIR), diffusion sampling |
Color | : | Matte White |
Electrical Wiring Size | : | Screw terminals, 18-24 AWG |
Enclosure Material | : | High impact ABS plastic |
Humidity Measurement Accuracy | : | ±2% from 10 to 80% RH @ 25°C (77 °F) |
IP Protection | : | IP20 |
Input Specifications | : | Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz |
Measurement Type | : | CO2 / Temperature |
Operating Current | : | 20mA |
Operating Humidity | : | 0 to 95% RH non-condensing |
Operating Temperature | : | 0 to 50 °C (32 to 122 °F) |
Output Specifications | : | Selectable 4 to 20 mA (2-wire), 0 to 5 V (3-wire), 0 to 10 V (3-wire) |
Outputs | : | Analog |
Standards EMC | : | EN61000 Series - industrial immunity |
Standards | : | CE, UL 916, RCM, ICES-003. REACH, RoHS |
Temperature Measurement Accuracy | : | ±0.3 °C (±0.54 °F) typical |
Temperature Measurement Range | : | 0 to 50 °C (32 to 122 °F) |
Temperature Measurement Resolution | : | 0.1 °C (0.1 °F) |
Temperature Sensor Type | : | 1000 Ohm Platinum RTD |
Warranty | : | 3 Years |
The CWE2 Series of air quality sensors for living space are for use with BAS controllers designed to accept 4 to 20mA, 0 to 5 Vdc or 0 to 10 Vdc outputs. These sensors measure CO2 levels using a dual-beam, non-dispersive infrared (NDIR) technology. The CWE2C measures temperature as well. The CWE2 Series Economy sensor has an accuracy of ±30 ppm ±3% of measured value, features 2-wire 4 to 20mA and 3-wire voltage outputs.