Application | : | Flow |
Connections | : | 1-1/2 in. Carbon Steel Mounting Assembly. Sealing Assembly: 2 Ethylene Propylene O-rings. |
Display Flow Rate | : | 6 Digits with Decimal; Totalizer |
Display Type | : | 2×16 Characters Reflective Display, Rotatable |
Fitting Size | : | 4" Pipe |
Flow Measurement Accuracy | : | ±1% of Reading |
Flow Measurement Range | : | 1 - 20 ft/s (0.3 - 6 m/s) |
Flow Measurement Repeatability | : | ±0.25% of Reading |
Flow Sensor Type | : | Dual Piezo Vortex Sensors |
Keypad | : | 4 Membrane Buttons |
Maximum Pressure | : | 1000 psi (68.9 bar) |
Measurement Interval | : | Second, Minute, Hour, Day (Selectable) |
Measurement Type | : | Flow |
Measuring Units | : | Pounds, Kilograms, Tons, Metric Tons, Cubic Feet, Cubic Meters, Gallons, Liters |
Media Temperature | : | -250 to 400 °F (-120 to 204 °C) |
Medium | : | Steam |
Operating Fluid Temperature | : | 14 - 150 °F (-10 - 65 °C) |
Operating Temperature | : | 32 to 140° F (0 to 60° C) |
Outputs | : | Pulse output. 4-20mA, Digital Output |
Product Type | : | Sensor |
Range | : | VN2000 |
Warranty | : | 1 year |
Wetted Materials | : | Stainless Steel 304L |
The VN2000 Compact Insertion Vortex Flow Meter measures the flow of
steam over a large flow range. The meter includes a mounting assembly
alignment pin to simplify the installation. The meter is designed for
specific pipe sizes and includes parts for installation. The vortex sensing
element is CNC machined out of one piece of solid stainless steel and
engineered to stand up to abusive environments inside and outside
the pipe. The dual ceramic piezoelectric sensors are bonded inside the
vortex element, which is press-fit to the stainless steel insertion bar and
completely welded together. There are no internal O-rings or seals of
any kind and absolutely no leak paths into the sensors or electronics.
These sensors do not touch the process fluid, which gives them an
almost unlimited life span.