CO2 Measurement Accuracy
|
:
|
±30 ppm ±3% of measured value
|
CO2 Measurement Range
|
:
|
0 to 2000/5000 ppm (selectable)
|
CO2 Measurement Repeatability
|
:
|
±20 ppm ±1% of measured value
|
CO2 Measurement Resolution
|
:
|
1 ppm
|
CO2 Response Time
|
:
|
<60 seconds for 90% step change
|
CO2 Sensor Type
|
:
|
Non-dispersive infrared (NDIR), diffusion sampling
|
Color
|
:
|
Matte White
|
Electrical Wiring Size
|
:
|
Screw terminals, 18-24 AWG
|
Enclosure Material
|
:
|
High impact ABS plastic
|
Humidity Calibration Certificate
|
:
|
Replaceable RH element available in 1% & 2% with NISTcalibration certificate
|
Humidity Measurement Accuracy
|
:
|
±2% from 10 to 80% RH @ 25°C (77 °F)
|
Humidity Measurement Linearity
|
:
|
Included in accuracy specification
|
Humidity Measurement Range
|
:
|
0 to 100% RH
|
Humidity Measurement Resolution
|
:
|
0.1% RH
|
Humidity Sensor Type
|
:
|
Thin-film capacitive, replaceable
|
IP Protection
|
:
|
IP20
|
Input Specifications
|
:
|
Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
|
Measurement Type
|
:
|
CO2 / VOC / RH / Temperature
|
Operating Humidity
|
:
|
0 to 95% RH non-condensing
|
Operating Temperature
|
:
|
0 to 50 °C (32 to 122 °F)
|
Output Specifications
|
:
|
Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
|
Outputs
|
:
|
Analog
|
Standards EMC
|
:
|
EN61000 Series - industrial immunity
|
Standards
|
:
|
CE, UL 916, RCM, ICES-003. REACH, RoHS
|
Temperature Measurement Accuracy
|
:
|
±0.2 °C (±0.4 °F) typical
|
Temperature Measurement Range
|
:
|
0 to 50 °C (32 to 122 °F)
|
Temperature Measurement Resolution
|
:
|
0.1 °C (0.1 °F)
|
Temperature Sensor Type
|
:
|
Solid state, integrated circuit
|
VOC Measurement Accuracy
|
:
|
±15% of measured value
|
VOC Measurement Range
|
:
|
0 to 100% AQI for VOC
|
VOC Output Scale
|
:
|
0 to 1,000 ppb of total VOC (TVOC)
|
VOC Sensor Type
|
:
|
Solid state
|