Application Zone | : | Plant Room |
Application | : | Pump and Compressor Differential Pressure | Chiller Differential Pressure Monitoring |
Brand | : | Veris |
Burst Pressure | : | 500 psi (34 bar) |
Calibration Certificate | : | No |
Dimension Depth | : | 2.6" (67 mm) |
Dimension Height | : | 12" (305 mm) |
Dimension Width | : | 8.7" (221 mm) |
Display Size | : | 0.7" x 1.4" (17 mm x 36 mm) |
Display Type | : | LCD |
Electrical Wiring | : | 3-wires |
Enclosure Material | : | Powder Coated Aluminium |
Fitting Material | : | Stainless Steel |
Fitting Size | : | 1/ 8” NPT |
Fitting Type | : | Female |
IP Protection | : | IP65 (NEMA 4) |
Measurement Type | : | Differential Pressure |
Medium | : | Water |
Model | : | PWLX04BP |
Mounting | : | Panel |
Operating Current | : | 125 - 280 mA |
Operating Humidity | : | 0 - 90% RH, non-condensing |
Operating Temperature | : | 14 - 122 °F (-10 - 50 °C) |
Output Specifications | : | 4 - 20 mA | 0 - 5 V | 0 - 10 V |
Outputs | : | Analog output |
Pressure Measurement Accuracy | : | Range A and B: ±1% of F.S. Range C: ±1.5% of F.S. Range D: ±2% of F.S. |
Pressure Measurement Range | : | 0 - 10 psi (0 - 0.7 bar) | 0 - 20 psi (0 - 1.4 bar) | 0 - 50 psi (0 - 3.5 bar) | 0 - 100 psi (0 - 7 bar) |
Product Certification | : | CE |
Product Type | : | Sensor |
Range | : | PW |
Standards EMC | : | EN 61000-6-1 |
Supply Voltage AC Nominal | : | 24 VAC |
Supply Voltage DC Range | : | 15 - 30 VDC |
Warranty | : | 5 years |
The PW series wet pressure transducers incorporate microprocessor profiled sensors for exceptional accuracy and reliability. Easy to use and designed to provide exceptional installation savings, the PW Series is ideal for measuring pressure across pumps, filters, heat exchangers, compressors and other non-corrosive wet media applications. The jumper-selectable port swap feature eliminates costly replumbing when the high and low ports are improperly plumbed, allowing the jumper position to be changed from normal to swap.
Optional Accessories: AA11, AA12, AA13