• We can help. Call 800-354-8556

Veris H934 Current Switch

Hawkeye 0.1 A at 30 VAC/VDC NO Split-Core VFD Current Sensor, SPST, NO

  • Brand Name: Veris
  • Veris Part#: H934
  • Est. Shipping Date: loading
Application      :      Building Automation Systems
Current Measurement Range      :      3.5 - 135 A
Current Sensor type      :      Current Switch, AC
Electrical Wiring Size      :      24 - 14 AWG (0.2 - 2.1 mm²)
Measurement Type      :      AC Current | VFD
Model      :      H934
Monitored Frequency Range      :      50 - 60 Hz
Monitored Wire Size      :      0.8" (21 mm)
Mounting      :      Split Core
Operating Humidity      :      10 - 90% RH, non-condensing
Operating Temperature      :      5 - 140 °F (-15 - 60 °C)
Output Specifications      :      N.O. 0.1 A @ 30 VAC/DC
Outputs      :      Switch output | Relay
Product Certification      :      UL | CE
Product Type      :      Sensor
Range      :      VFD Series
Relay Coil Voltage      :      24 VAC/DC
Relay Construction      :      Mechanical
Relay Contact Ratings      :      Resistive: 5 A @ 250 VAC | Resistive: 5 A @ 30 VDC
Relay Poles/Throw      :      SPST
Setpoint      :      Automatic Calibration
Warranty      :      5 years

Hawkeye 934 current monitoring devices provide unique solutions for accurately monitoring status of motors controlled by variable frequency drives. The microprocessor based H934 store the sensed amperage values for normal operation at various frequency ranges in non-volatile memory. This information allows the device to distinguish between a reduced amp draw due to normal changes in the frequency and an abnormal amp drop due to belt loss or other mechanical failures. The relay on the H934 is isolated from the current switch, and all relay connections are externally accessible on the device.

  • Automatically compensates for the effects of frequency and amperage changes in monitored conductor associated with VFDs
  • Nuisance reduction - provides a secondary setpoint option of 50% of the originally measured current
  • Rapid troubleshooting - LED indicates normal and alarm conditions
  • Induced from monitored conductor sensor power
  • LED status, LED relay power
  • pdf Datasheet https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/H720_H904_H934_d0321.pdf
  • word Engineering Specs https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/h934e_06121.docx
  • pdf Installation Guide https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/H934_I0F2.pdf