• We can help. Call 800-354-8556

Veris HT1NAS1C Humidistats

ABS Plastic +/-1% NIST 1 kOhm Platinum RTD Humidistat and Thermostat Control, 1-Point Calibration, Analog Setpoint

  • Brand Name: Veris
  • Veris Part#: HT1NAS1C
  • Est. Shipping Date: loading
Application Zone      :      Living Space
Color      :      Cloud White
Display Size      :      1.2" x 0.6" (30.5 mm x 14 mm)
Display Type      :      LCD
Humidity Calibration Certificate      :      NIST
Humidity Measurement Accuracy      :      ±1%
Humidity Setpoint Range      :      0 - 100% RH
Measurement Type      :      Temperature | Humidity
Model      :      HT1NAS1C
Mounting      :      Wall
Output Specifications      :      4 - 20 mA | 0 - 5 V | 0 - 10 V
Outputs      :      Analog output | Resistive temperature output
Override      :      No
Product Certification      :      CE
Product Type      :      Humidistat | Thermostat
Range      :      HWS
Setpoint      :      Yes
Temperature Calibration Certificate      :      1 pt
Temperature Measurement Accuracy      :      ±0.6 °F (±0.3 °C)
Temperature Measurement Range      :      32 - 122 °F (0 - 50 °C)
Temperature Measurement Resolution      :      0.1 °
Temperature Sensor Type      :      1k Ohm Platinum RTD
Temperature Setpoint Range      :      50 - 95 °F (10 - 35 °C) | 32 - 122 °F (0 - 50 °C)
Warranty      :      5 years (1 year on replaceable RH element)

All HT series institutional grade relative humidity transmitters are designed to meet the rigorous needs of pharmaceutical labs, hospitals, science labs and other settings that call for precise environmental control. Internal jumpers control access to a feature that allows adjustment of the calibration offsets. The devices can also be made tamper resistant using a jumper to disable keypad programing functions. HT models are calibrated with NIST traceable calibration equipment. Analog output models feature a keypad to make adjusting humidity and temperature setpoint values easy. They transmit the setpoint values back to a control system by means of dual outputs. A slide-switch allows easy selection of output type, either 4 to 20 mA or 0 to 5 V/0 to 10 VDC signals. Dual outputs enable effortless control of both humidity and temperature in a single, compact sensor.

  • Analog setpoint outputs (TWS analog) provide application flexibility
  • LCD for local display of readings and setup values
  • Offset function adjusts calibration intervals for both RH and T
  • Switch-selectable 4 to 20 mA or 0 to 5/0 to 10 VDC analog outputs
  • Multi-point calibration to 1% RH, traceable to NIST
  • Saves time - replaceable RH sensor element supports field calibration offset
  • 1% NIST
  • Analog setpoint
  • 1-point calibration temperature certificate
  • Digitally profiled thin-film capacitive (32-bit mathematics) US Patent 5,844,138 RH sensor
  • pdf CE Declaration https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/hta-CEDec02081.pdf
  • pdf Datasheet https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/HT_HWS_d0117.pdf
  • pdf Installation Guide https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/ht-analog_i0r2.pdf