• We can help. Call 800-354-8556

Veris E51H2A Advanced Power Meter

Alarm/BACnet MS/TP Output 1-Pulse Input Bi-Directional Compact Power and Energy Meter

  • Brand Name: Veris
  • Veris Part#: E51H2A
  • Est. Shipping Date: loading
Accuracy      :      +/- 0.2%
Communication      :      BACnet (MS/TP)
Dimensions      :      3.6" (91 mm) W x 4.2" (107 mm) W x 2.3" (59 mm) H
Display Type      :      LCD
Environmental Conditions      :      Humidity Range: Less Than 95% RH Non-Condensing; Storage Temperature: -40 to 158 °F; Altitude of Operation: 3000 m
Frequency Rating      :      50 - 60 Hz
Metering Product Family      :      E50 Power Meter
Monitored Voltage Range      :      90 - 600 VAC
Mounting      :      Din-Rail
Operating Temperature      :      -22 - 158 °F
Output Specifications      :      Alarm: 30 VAC/VDC, 100 mA Maximum (NC); BACnet MS/TP
Product Type      :      Bi-Directional Compact Power and Energy Meter
Range      :      E51

The E51H2A DIN rail power meters provide a solution for measuring energy data with a single device. Inputs include control power, CT and 3-phase voltage. Models support BACnet MS/TP protocol. The E51H2A has one pulse contact input and a phase loss alarm output. The LCD screen on the faceplate allows instant output viewing. The E51 meters are capable of bidirectional metering. Power is monitored in both directions (upstream and downstream from the meter). The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN 50022. The E51 can be mounted either on a DIN rail or in a panel.

  • Alarm output (normally close)
  • Full data set output
  • RS-485 serial (BACnet MS/TP protocol) output
  • 1 pulse input: solid-state or mechanical contacts (current less than 1 mA)
  • pdf CE Declaration https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/CE Declaration - E50 and E51 - ECDE5xDoC_-_V1.0.pdf
  • pdf Datasheet https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/E5xxxA_d0324.pdf
  • pdf Installation Guide https://www.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/e51hxa_full_i0d2.pdf