Application | : | Building Automation Systems |
Current Measurement Accuracy | : | ±2% of F.S. above 10% of F.S. |
Current Measurement Range | : | 0 - 30 A | 0 - 60 A | 0 - 120 A |
Current Sensor type | : | Current Transducer, AC |
Electrical Wiring Size | : | 24 - 14 AWG (0.2 - 2.1 mm²) |
Measurement Type | : | AC Current |
Model | : | H923 |
Monitored Frequency Range | : | 50 - 60 Hz |
Monitored Wire Size | : | 0.8" (21 mm) |
Mounting | : | Split Core |
Operating Humidity | : | 10 - 90% RH, non-condensing |
Operating Temperature | : | 5 - 140 °F (-15 - 60 °C) |
Output Specifications | : | 0 - 10 VDC |
Outputs | : | Analog output |
Product Certification | : | UL | CE |
Product Type | : | Sensor |
Range | : | HX23 Series |
Relay Coil Voltage | : | None |
Relay Contact Ratings | : | None |
Relay Poles/Throw | : | None |
Warranty | : | 5 years |
The Hawkeye 923 provide accurate load trending information with a proportional 0 to 10 VDC output signal. Slide-switches provide easy field selection of monitored amperage range without jumpers.