Application | : | Building Automation Systems |
Current Measurement Accuracy | : | ±2% of F.S. above 30 A |
Current Measurement Range | : | 0 - 300 A |
Current Sensor type | : | Current Transducer, AC |
Electrical Wiring Size | : | 22 - 12 AWG (0.33 - 3.3 mm²) |
Measurement Type | : | AC Current |
Model | : | H221SP |
Monitored Frequency Range | : | 50 - 60 Hz |
Monitored Wire Size | : | 1.4" (35 mm) |
Mounting | : | Split Core |
Operating Humidity | : | 10 - 90% RH, non-condensing |
Operating Temperature | : | 5 - 140 °F (-15 - 60 °C) |
Output Specifications | : | 4 - 20 mA |
Outputs | : | Analog output |
Product Certification | : | UL | CE |
Product Type | : | Sensor |
Range | : | High Current Series |
Relay Coil Voltage | : | None |
Relay Contact Ratings | : | None |
Relay Poles/Throw | : | None |
Warranty | : | 5 years |
Hawkeye H221SP analog current transducers provide reliable load trending information for large motor loads (up to 2400 A), with a proportional 4 to 20 mA signal. The H221SP versions are factory-calibrated at a range specified by the customer.