Application Zone | : | Living Space |
Application | : | Wall |
Brand | : | Veris |
CO2 Measurement Accuracy | : | ±30 ppm ±2% of measured value |
CO2 Measurement Range | : | 0 - 5000 ppm |
CO2 Measurement Repeatability | : | ±20 ppm ±1% of measured value |
CO2 Measurement Resolution | : | 1 ppm |
CO2 Sensor Type | : | NDIR |
Color | : | Cloud White |
Communication | : | BACnet (MS/TP) | Modbus (RTU) |
Dimension Depth | : | 1.2" (30 mm) |
Dimension Height | : | 4.8" (122 mm) |
Dimension Width | : | 3.5" (89 mm) |
Display Resolution | : | 2 Rows x 8 Characters |
Display Size | : | 1.2" x 0.6" (30,5 mm x 14 mm) |
Display Type | : | LCD |
Electrical Wiring Size | : | 24 - 18 AWG (0.22 - 0.75 mm²) |
Enclosure Material | : | ABS Plastic |
Humidity Calibration Certificate | : | None |
Humidity Measurement Accuracy | : | ±2% |
Humidity Measurement Range | : | 0 - 100% RH |
Humidity Measurement Resolution | : | 0.1% RH |
Measurement Type | : | CO2 | Humidity | Temperature |
Mounting | : | Wall |
Operating Humidity | : | 0 - 95% RH, non-condensing |
Operating Temperature | : | 50 - 95 °F (10 - 35 °C) |
Outputs | : | Protocol Communication |
Override | : | No |
Product Certification | : | CE |
Product Type | : | Sensor |
Range | : | CWxP |
Response Time | : | CO2: <60 seconds for 90% step change |
Setpoint | : | No |
Supply Voltage AC Nominal | : | 24 VAC |
Supply Voltage DC Nominal | : | 12 - 30 VDC |
Temperature Calibration Certificate | : | 1 pt |
Temperature Sensor Type | : | None |
Warranty | : | 5 years |
CW Protocol series is a non-dispersive infrared (NDIR) sensor designed for measuring CO2 concentration in ventilation systems and indoor living spaces. Its measurement range of 0 to 5000 ppm makes it the premier solution for meeting ASHRAE and other ventilation efficiency standards. CW Protocol devices feature embedded BACnet and Modbus communication protocols, as well as optional temperature and humidity sensors. An adjustable setpoint relay is provided for direct control and alarm applications and the optional setpoint slider and pushbutton override offer additional local input.