Application | : | Water and Leak detection for BAS applications |
Leak Detection Sensor Type | : | Controller |
Model | : | LD310 |
Operating Altitude | : | 15,000' (4572 m) max. |
Operating Temperature | : | 32 - 122 °F (0 - 50 °C) |
Outputs | : | Relay |
Product Certification | : | CE | ETL |
Product Type | : | Control panel |
Range | : | Leak Detection |
Relay Contact Ratings | : | 1 A @ 24 VDC | 0.5 A @ 120 VAC |
Warranty | : | 2 years |
LD310 control panels continuously monitor 300 ft for the LD310 of SC or SC-C detection cable per zone. If the cable detects fluid at any point along its length, the detection panel illuminates the corresponding zone LED, clearly indicating which zone is affected. An alarm (visual for LD310, audible for all others) signals the presence of a leak. Additionally, if the cable loses continuity, the panel will activate a cable fault LED. The detection sensitivity can be set independently for each zone. A summary alarm relay output is standard.