The VT7600H PI thermostat family is designed for multi-stage control of heating/cooling equipment such as heat pumps and self-contained units. The product features an intuitive, menu-driven, back-lit LCD display which walks users through the programming steps, making the process extremely simple. All models contain two user-controlled digital inputs that monitor filter status, change the occupancy status, and/or provide general purpose service indication. Some models include up to three remote sensor inputs. All devices are available with Echelon, BACnet, or wireless adapters.

APPLICATIONS
  • Single speed fans
  • Supply air temperature sensor
  • Outdoor air temperature sensor
  • Differential pressure switch
Features
  • PI time proportioning algorithm...increased comfort, accuracy, and energy savings
  • Smart fan...saves energy during night mode
  • Unique local configuration utility...minimizes parameter tampering
  • Lockable keypad...tamper proof, no need for thermostat guards
  • Freeze protection...prevents costly freeze damage
  • EEPROM memory...no loss of program
  • 6 hour reserve time for clock...no need to reprogram day or time after power outage
  • Auxiliary output...can be used for lighting and/or economizer override
  • Discharge air sensor...can be used to monitor unit efficiency
  • Low/High balance point...protect and optimize system performance
  • 3 Heat/2 Cool...support single and two stages heat pump with one auxiliary heat stage
  • Thermostat Power Requirements 19-30 VAC 50 or 60 Hz; 2 VA Class 2
  • Operating Conditions 0° to 50°C (32° to 122°F); 0% to 95% R.H. non-condensing
  • Storage Conditions -30° to 50°C (-22° to 122°F); 0% to 95% R.H. non-condensing
  • Temperature Sensor Local 10 K NTC thermistor
  • Resolution ± 0.1°C (± 0.2°F)
  • Control Accuracy Temp: ±0.5°C (±0.9°F ) @ 21°C (70°F) typical, calibrated
  • Occupied and Unoccupied Setpoint Range Cooling 12.0° to 37.5°C (54° to 100°F)
  • Occupied and Unoccupied Setpoint Range Heating 4.5° to 32°C (40° to 90°F)
  • Room and Outdoor Air Temperature Display -40° to 50°C (-40° to 122°F)
  • Proportional Band for Room Temperature Range Control Cooling & Heating: 1.8°C (3.2°F )
  • Binary Inputs Dry contact across terminal BI1, BI2 & UI3 to Scom
  • Outputs Rating Triac output: 30 VAC, 1 Amp max., 3 Amp in-rush; Analog: 0 to 10 VDC into 2k? resistance min.
  • Economizer Analog Output Rating 0 to 10 VDC into 2k? resistance min.
  • Economizer Analog Output Accuracy ±3% typical
  • Wire Gauge 18 gauge maximum, 22 gauge recommended
  • Dimensions 4.94” x 3.38” x 1.13”
  • Approximate Shipping Weight 0.75 lb (0.34 kg)
Agency Approvals:
  • UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN, XAPX (US) and XAPX7 (Canada)
  • FCC Compliant to CFR 47, Part 15, Subpart B, Class A (US)
  • Industry Canada ICES-003 (Canada)
  • CE EMC Directive 89/336/EEC (Europe Union)
  • C-Tick AS/NZS CISPR 22 Compliant (Australia / New Zealand), Supplier Code Number N10696